3 VLT Automation VT Drive Selection
FC322, P18KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
36
480
0.396
100
480
0.844
150
480
0.696
3
FC322, P22KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
36
480
0.312
100
480
0.556
150
480
0.608
FC322, P30KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
15
480
0.288
100
480
0.492
150
480
0.468
FC322, P37KT4
Cable
Mains
Rise time
length [m]
voltage
[μsec]
5
480
0.368
50
480
0.536
100
480
0.680
150
480
0.712
FC322, P45KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
5
480
0.368
50
480
0.536
100
480
0.680
150
480
0.712
FC322, P55KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
15
480
0.256
50
480
0.328
100
480
0.456
150
480
0.960
FC322, P75KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
5
480
0.371
70
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Vpeak
dU/dt
[kV]
[kV/μsec]
1.210
2.444
1.230
1.165
1.160
1.333
Vpeak
dU/dt
[kV]
[kV/μsec]
2.846
1.250
1.798
1.230
1.618
Vpeak
dU/dt
[kV]
[kV/μsec]
3.083
1.230
2.000
1.190
2.034
Vpeak
dU/dt
[kV]
[kV/μsec]
1.270
2.853
1.260
1.978
1.240
1.426
1.200
1.334
Vpeak
dU/dt
[kV]
[kV/μsec]
1.270
2.853
1.260
1.978
1.240
1.426
1.200
1.334
Vpeak
dU/dt
[kV]
[kV/μsec]
1.230
3.847
1.200
2.957
1.200
2.127
1.150
1.052
Vpeak
dU/dt
[kV]
[kV/μsec]
1.170
2.523
®
is a registered Danfoss trademark