3 VLT Automation VT Drive Selection
The maximum depth and width are as required by the installation. When using multiple frequency converters in one enclosure it is recommended that
each drive is mounted on its own back panel and supported along the mid-section of the panel. These duct work kits do not support the "in frame"
mounting of the panel (see Rittal TS8 catalogue for details). The duct work cooling kits listed in the table below are suitable for use only with IP 00 /
Chassis frequency converters in Rittal TS8 IP 20 and UL and NEMA 1 and IP 54 and UL and NEMA 12 enclosures.
For the E2 frames it is important to mount the plate at the absolute rear of the Rittal enclosure due to the weight of the frequency
converter.
3
NB!
A door-fan(s) is required on the Rittal cabinet to remove the loses not contained in the back-channel of the drive. The minimum door-
fan(s) airflow required at the drive maximum ambient for the D3 and D4 is 391 m^3/h (230 cfm). The minimum door-fan(s) airflow
required at the drive maximum ambient for the E2 is 782 m^3/h (460 cfm). If the ambient is below maximum or if additional compo-
nents, heat loses, are added within the enclosure a calculation must be made to ensure the proper airflow is provided to cool the inside
of the Rittal enclosure.
Ordering Information
Rittal TS-8 Enclosure
Frame D3 Kit Part No.
1800 mm
176F1824
2000 mm
176F1826
2200 mm
Kit Contents
Ductwork components
Mounting hardware
Gasket material
Delivered with D3 and D4 frame kits:
175R5639 - Mounting templates and top/bottom cut out for Rittal enclosure.
Delivered with E2 frame kits:
175R1036 - Mounting templates and top/bottom cut out for Rittal enclosure.
All fasteners are either:
10 mm, M5 Nuts torque to 2.3 Nm (20 in-lbs)
T25 Torx screws torque to 2.3 Nm (20 in-lbs)
NB!
Please see the
Duct Kit Instruction Manual, 175R5640,
External ducts
If additional duct work is added externally to the Rittal cabinet the pressure drop in the ducting must be calculated. Use the charts below to derate the
frequency converter according to the pressure drop.
96
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
Automation VT Drive FC322 Design Guide
Frame D4Kit Part No.
Frame E2 Part No.
176F1823
Not possible
176F1825
176F1850
176F0299
for further information
®