MAKING MODERN LIVING POSSIBLE Quick Guide ® AutomationDrive FC 360...
Page 3
The amount of wait time is listed in the Discharge Time table. Failure to wait the specified time after power has been removed before doing service or repair could result in death or serious injury. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 4
® Safety AutomationDrive FC 360 Quick Guide ® MG06A102 - VLT is a registered Danfoss trademark...
4.1.1 Programming with the Numerical Local Control Panel (NLCP) 4.1.2 NLCP 4.1.3 The Right-Key Function 4.2 Quick Menu 4.3 Main Menu 4.4 Parameter List 4.4.1 Main Menu Structure 5 Wiring Examples 6 Warnings and Alarms 6.1 System Monitoring ® MG06A102 - VLT is a registered Danfoss trademark...
Page 6
7.1 Start Up and Operation 8 Specifications 8.1 Power-dependent Specifications 8.1.1 Mains Supply 3 x 380-480 V AC 8.2 General Technical Data 8.3 Fuse Specifications 8.3.2 Recommendations 8.3.3 CE Compliance 8.4 Connection Tightening Torques Index ® MG06A102 - VLT is a registered Danfoss trademark...
All selections are for Auto On mode. Table 1.2 NOTE When an application is selected, relevant parameters are automatically set. Further setups to all parameters based on specific requirements is still possible. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 9
6-91 (AO42): [103] Motor current 6-19 (AI 53 Mode) [1] Voltage Mode Table 1.4 6-22 (AI 54 Low) 4.0 mA 6-23 (AI 54 High) 20.0 mA 6-29 (AI 54 Mode) [0] Current Mode ® MG06A102 - VLT is a registered Danfoss trademark...
Page 10
6-11 (AI 53 High): 10 V Table 1.6 6-19 (AI 53 Mode): [1] Voltage Mode 7-00 (Speed PID Feedback Source): [1] 24 V encoder NOTE Table 1.5 For further examples refer to 5 Wiring Examples. ® MG06A102 - VLT is a registered Danfoss trademark...
Set motor cable length in 1-42 Motor Cable Length Go to 1-29 Automatic Motor Adaptation (AMA). Press [OK]. Select [1] Enable complete AMA. Press [OK]. The test will run automatically and indicate when it is complete. ® MG06A102 - VLT is a registered Danfoss trademark...
Shielded cable grounding clamp and strain relief Fixed I/O terminals (accessory) Motor terminal (U V W) and brake and load sharing Terminal cover terminal PE ground Option-B (MCB102/103 accessories) 3-Pole relay 1 Table 2.1 ® MG06A102 - VLT is a registered Danfoss trademark...
Contact the local Danfoss supplier or go to efficiency, and offers many more control, monitoring, and http://www.danfoss.com/Products/Literature/VLT+Technical efficiency functions. Operation and monitoring functions +Documentation.htm for downloads.
Improper mounting can result in over heating and reduced performance • Use the slotted mounting holes on the unit for wall mounting, when provided • See 8.4 Connection Tightening Torques for proper tightening specifications. ® MG06A102 - VLT is a registered Danfoss trademark...
1) Built-in braking chopper available from 0.37 - 22 kW 2) Relay 2 is 2 pole for J1-J3 and 3 pole for J4-J7. Relay 2 of J4-J7 with terminal 4,5,6, same NO/NC logic as Relay 1. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 16
Motor, 3-phase and PE Output contactor (Generally not recommended) Mains, 3-phase and reinforced PE Earth (grounding) rail (PE) Control wiring Cable insulation (stripped) Equalising min. 16 mm (0.025 in) Table 3.2 ® MG06A102 - VLT is a registered Danfoss trademark...
• All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements. • Danfoss recommends that all power connections be made with a minimum 75° C rated copper wire. Illustration 3.3 Grounding Principle • See 8 Specifications for recommended wire sizes.
IEC 61800-3. • Do not install switch between the frequency converter and the motor in IT mains. Illustration 3.5 Control Wiring Access for J1-J7 Enclosures ® MG06A102 - VLT is a registered Danfoss trademark...
6-91 [0] No operation Programmable analog output. The analog signal 6-71 [0] No operation is 0-20mA or 4-20 mA at a maximum of 500Ω. Can also be configured as digital outputs ® MG06A102 - VLT is a registered Danfoss trademark...
50/60Hz ground loops With very long control cables, ground loops may occur. To eliminate ground loops, connect one end of the screen-to- ground with a 100nF capacitor (keeping leads short). 100nF Illustration 3.8 ® MG06A102 - VLT is a registered Danfoss trademark...
RS-485 connection or in parameter group 8-** Communications and Options • Selecting a specific communication protocol changes various default parameter settings to match that protocol’s specifications along with making additional protocol-specific parameters available ® MG06A102 - VLT is a registered Danfoss trademark...
PC via RS-485 com-port by installing the MCT-10 Setup counterclockwise. software. This software can either be ordered using code The triangle indicates if the LCP is in status, quick menu or number 130B1000 or downloaded from the Danfoss Web main menu. site: www.danfoss.com/BusinessAreas/DrivesSolutions/ Table 4.1 softwaredownload 4.1.2 NLCP...
The right key can also be used for moving between parameter groups: when in main menu, press the right key to move to the first parameter in the next parameter group (e.g. move from 0-03 [0] to 1-00 [0]). ® MG06A102 - VLT is a registered Danfoss trademark...
Press [OK] to accept the change. To exit, press either [Back] twice (or three times if in QM” and QM3) to enter Status, or press [Menu] once to enter Main Menu. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 25
® User Interface and Programm... AutomationDrive FC 360 Quick Guide ® MG06A102 - VLT is a registered Danfoss trademark...
]: select parameter within the group. [Back]: Removes the value and shows the parameter group. Setup 1 ▲ ▼ ]: select group. Table 4.5 Illustration 4.5 Main Menu Interactions - Continuous Parameters ® MG06A102 - VLT is a registered Danfoss trademark...
[Back]: cancels editing index, a new parameter can be selected. ▲ ▼ ]: selects parameter within the group. [Back]: removes parameter index value and shows the parameter group. ▲ ▼ ]: selects group. Table 4.6 ® MG06A102 - VLT is a registered Danfoss trademark...
Preset ref. 2 A OUT Notes/comments: -10 - +10V Preset ref. 3 100% * = Default Value Notes/comments: Table 5.2 Analog Speed Reference (Voltage) Table 5.4 Start/Stop with Reversing and 4 Preset Speeds ® MG06A102 - VLT is a registered Danfoss trademark...
Page 33
5 sec. then the drive continues and the warning disappears. But Relay 1 will still be triggered until [Reset] on the LCP. Table 5.7 Using SLC to Set a Relay ® MG06A102 - VLT is a registered Danfoss trademark...
Page 34
S p e e d u p ( 2 9 ) S p e e d d o w n ( 3 2 ) Illustration 5.1 CAUTION Thermistors must use reinforced or double insulation to meet PELV insulation requirements. ® MG06A102 - VLT is a registered Danfoss trademark...
Very serious faults cause alarms with trip lock which require that input power be cycled before resetting the alarm in any of the 4 ways described above. Hand Auto Reset Illustration 6.3 ® MG06A102 - VLT is a registered Danfoss trademark...
Wrong setting for motor voltage and/or motor current. AMA low I Motor current is too low. Check settings. AMA big motor The motor is too big for the AMA to operate. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 37
A wrong password was entered Occurs when using a wrong password for changing a password-protected parameter. These faults may be caused by mains distortions. Installing Danfoss Line Filter may rectify this problem. Table 6.1 Warnings and Alarms Code List ®...
Possible incorrect settings in the Check brake parameters. Check Check parameter group2-0* DC Motor will not brake brake parameters. Possible too ramp time settings. brake and 3-0* Reference limits. short ramp down times. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 39
Resonances, e.g. in the motor/fan have been reduced to an Change switching pattern and noise or vibrations at system acceptable limit. frequency in parameter group certain frequencies) 14-0*. Increase Resonance Dampening in 1-64. Table 7.1 ® MG06A102 - VLT is a registered Danfoss trademark...
85 mm brake) [mm / AWG] Estimated power loss at rated max. load [W] Weight enclosure IP20 [kg] 12.3 12.5 Efficiency Table 8.2 Mains Supply 3x380-480 V AC - Heavy Duty ® MG06A102 - VLT is a registered Danfoss trademark...
Page 41
Although measurements are made with state of the art equipment, some measurement inaccuracy must be allowed for ( 4) Measured using 5 m screened motor cables at rated load and rated frequency. ® MG06A102 - VLT is a registered Danfoss trademark...
Voltage level, logic'1' PNP > 10 V DC Voltage level, logic '0' NPN > 19 V DC Voltage level, logic '1' NPN < 14 V DC Maximum voltage on input 28 V DC ® MG06A102 - VLT is a registered Danfoss trademark...
Page 43
Accuracy on analog output Max. error: 0.8 % of full scale Resolution on analog output 10 bit The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. ® MG06A102 - VLT is a registered Danfoss trademark...
Page 44
System response time (terminals 18, 19, 27, 29, 32, 33) Speed control range (open loop) 1:100 of synchronous speed 30-4000 RPM: Maximum error of ±8 RPM Speed accuracy (open loop) All control characteristics are based on a 4-pole asynchronous motor ® MG06A102 - VLT is a registered Danfoss trademark...
Page 45
Monitoring of the intermediate circuit voltage ensures that the frequency converter trips if the intermediate circuit voltage is too low or too high. • The frequency converter is protected against earth faults on motor terminals U, V, W. ® MG06A102 - VLT is a registered Danfoss trademark...
NOTE The recommendations given do not cover Branch circuit protection for UL. Short-circuit protection Danfoss recommends using the fuses/Circuit Breakers mentioned below to protect service personnel and property in case of component break-down in the frequency converter. ® MG06A102 - VLT...
NEC 2009. We recommend using a selection of the Fuses or Circuit Breakers are mandatory to comply with IEC following 60364. Danfoss recommend using a selection of the following. The circuit breakers below are suitable for use on a circuit...
Use a torque wrench to ensure correct torque Frame Power [kW] Torque [Nm] size Mains Motor Brake Earth Relay connection 0.37-2.2 3.0 -55 11-15 18.5-22 30-45 Table 8.8 Tightening of Terminals ® MG06A102 - VLT is a registered Danfoss trademark...