Danfoss VLT AutomationVTDrive FC322 Design Manual page 72

Hide thumbs Also See for VLT AutomationVTDrive FC322:
Table of Contents

Advertisement

Automation VT Drive FC322 Design Guide
FC322, P90KT4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
5
480
0.371
High Power Range:
FC322, P110 - P250, T4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
30
400
0.34
FC322, P315 - P1M0, T4
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
30
500
0.71
30
400
0.61
FC322, P110 - P400, T7
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
30
690
0.38
30
575
0.23
30
1.72
690
1)
1) With Danfoss dU/dt filter.
FC322, P450 - P1M2, T7
Cable
Mains
Rise time
length [m]
voltage [V]
[μsec]
30
690
0.57
30
575
0.25
30
1)
1.13
690
1) With Danfoss dU/dt filter.
MG.20.X1.22 - VLT
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20783-Danfoss-131X8145-VLT-Automation-VT-Drive-VFD-FC322-460V-.5-HP.aspx
3 VLT Automation VT Drive Selection
Vpeak
dU/dt
[kV]
[kV/μsec]
1.170
2.523
Vpeak
dU/dt
[kV]
[kV/μsec]
1.040
2.447
Vpeak
dU/dt
[kV]
[kV/μsec]
1.165
1.389
0.942
1.233
Vpeak
dU/dt
[kV]
[kV/μsec]
1.513
3.304
1.313
2.750
1.329
0.640
Vpeak
dU/dt
[kV]
[kV/μsec]
1.611
2.261
2.510
1.629
1.150
®
is a registered Danfoss trademark