2. Commissioning

2.5.2 Select GSDML file (compatibility table)

GSDML file
Bus node
(Version)
(CPX revision code;
see label)
Rev 12 ... Rev 18
GSDML file
2)
V. 2.2
GSDML file
Rev 20 ... Rev 23
V. 2.25
1) The CPX revision code is located on the rating plate (see section 1.2).
2) The GSDML file V. 2.2 also supports bus nodes with Rev 07 ... Rev 11:
The additional function FSU is not supported by these bus nodes (with Rev 07 ... Rev 11).
3) Individual bus nodes with Rev 13 do not have the required hardware to support the additional
function FSU. Required hardware revision: > 8. Check the hardware revision status using CPX-FMT
or contact your local Festo Service.
4) The additional function FSU is only supported by bus nodes from Rev 12 onward.
Tab. 2/10: Compatibility of GSDML file, bus nodes and controller
Festo P.BE-CPX-PNIO-EN en 1407c English
Using the subsequent compatibility table, select the required
GSDML file for your system and application purpose.
Controller software
(PLC software status)
1)
3)
Siemens STEP 7:
from Version 5.4,
Service Pack SP4
Siemens STEP 7:
from Version 5.4,
Service Pack SP4 or
"TIA-Portal"
The current GSDML file for CPX terminals can be found in the
Festo Support Portal:
www.festo.com/sp
Consult your local Festo repair service if you have any ques-
tions or technical problems.
Function range
(Extract)
"Fast start-up" (FSU)
expansion of module
support and diagnostic
function, in particular
regarding FOC diagnostics
PROFIenergy, PROFIsafe,
media redundancy
(MRP), shared device
Section 2.5.1.
4)
,
2-23