▼ To Fully Power On Fabric Cards
●
To bring a fabric card to full power, type this command:
# activate fc slot
where slot is the slot number of the fabric card from
When a fabric card is activated, the OK LED is illuminated and the fabric card
goes to full power.
▼ To Power Down Fabric Cards to a Standby State
●
To power down a fabric card to a standby state, type this command:
# deactivate fc slot
where slot is the slot number of the fabric card from
When a fabric card is deactivated, the OK LED turns off, but the Standby LED
remains flashing.
▼ To Read Fabric Card FRUID Information
●
To read the FRUID information of a fabric card, type this command:
# clia fruinfo ipmb-address 0
where ipmb-address is the IPMB address of the fabric card from
The following sample is a portion of the output for fabric card 3:
# clia fruinfo b8 0
Pigeon Point Shelf Manager Command Line Interpreter
b8: FRU # 0, FRU Info
Common Header:
Board Info Area:
Version
Language Code
Mfg Date/Time
Board Manufacturer
Board Product Name
Board Serial Number
Board Part Number
70
Sun Datacenter Switch 3456 Installation Guide • December 2008
Format Version = 1
= 1
= 25
= May 28 15:08:00 2008 (6525548 minutes since 1996)
= Sun Microsystems, Inc.
= DCS 3456 - Fabric Card
= 37535620821BT00030
= 375-3562-02
.
TABLE 8-1
.
TABLE 8-1
.
TABLE 8-1