To check the status of the CMCs, type this command:
# clia shmstatus
For example:
# clia shmstatus -v
Pigeon Point Shelf Manager Command Line Interpreter
Host: "Active"
Ready For Operation: Yes
Detailed State Flags: "Shelf FRU Found" "Backup Healthy" "Initial
Update Sent" "RMCP Up"
#
Powering On the Sun Datacenter Switch
3456
Powering on the Sun Datacenter Switch 3456 is a sequential process.

▼ To Power On the Sun Datacenter Switch 3456

1. Verify that all installed power supplies have a green Connected LED lit.
If the Connect LED is not lit, or the amber Attention LED is lit, investigate why.
2. Establish a connection to the CMCs.
See
"Working With CMCs" on page
3. Verify all installed components are recognized as installed, type:
# showpresent
If an installed component is not recognized, investigate why. See the Sun
Datacenter Switch 3456 Administration Guide and Sun Datacenter Switch 3456 Service
Manual for further assistance.
4. Power on each power supply, type:
# enablepsu slot
where slot is 0 to 15.