Installing the Avaya G450 Media Gateway
!
WARNING:
For installations in Finland, Norway, and Sweden, the Avaya G450 Media
WARNING:
Gateway relies on two ground connections (mains plug with an earth contact and
a Supplementary Ground Conductor).

Approved grounds

An approved ground is the closest acceptable medium for grounding the building entrance
protector, entrance cable shield, or a single-point ground of electronic telephony equipment. If
more than one type of approved ground is available on the premises, the grounds must be
bonded together as required in Section 250-81 of the NEC for the US or per the local electrical
code regulations in the country of installation.
Grounded Building Steel. The metal frame of the building where it is effectively grounded
by one of the following grounds: acceptable metallic water pipe, concrete encased ground,
or a ground ring.
Acceptable Water Pipe. A metal underground water pipe, at least 1/2 in (1.3 cm) in
diameter, in direct contact with the earth for at least 10 ft (3m). The pipe must be
electrically continuous (or made electrically continuous by bonding around insulated joints,
plastic pipe, or plastic water meters) to the point where the protector ground wire connects.
A metallic underground water pipe must be supplemented by the metal frame of the
building, a concrete-encased ground, or a ground ring. If these grounds are not available,
the water pipe ground can be supplemented by one of the following types of grounds:
- Other local metal underground systems or structures, such as tanks and piping
systems.
- Rod and pipe electrodes. A 5/8 in (1.6 cm) solid rod or 3/4 in (2 cm) conduit or pipe
electrode driven to a minimum depth of 8 ft (2.4 m).
- Plate electrodes. Must have a minimum of 2 sq. ft (0.185 sq. m) of metallic surface
exposed to the exterior soil.
Concrete Encased Ground. An electrode encased by at least 2 in (5.1 cm) of concrete and
located within and near the bottom of a concrete foundation or footing in direct contact with
the earth. The electrode must be at least 20 ft (6.1 m) of one or more steel reinforcing bars
or rods, 1/2 in (1.3 cm) in diameter, or at least 20 ft (6.1 m) of bare solid copper, 4 AWG (26
2
mm
) wire.
Ground Ring. A buried ground that encircles a building or structure at a depth of at least
2.5 ft (0.76 m) below the earth's surface. The ground ring must be at least 20 ft (6.1 m) of
2 AWG (35 mm
Approved Floor Grounds. Floor grounds are those grounds on each floor of a high-rise
building that are suitable for connection to the ground terminal in the riser closet and to the
cabinet single-point ground terminal. Approved floor grounds may include the following:
- Building steel.
42 Installation and Upgrades for the Avaya G450 Media Gateway
2
), bare copper wire.