Using The Ethernet Connection And Modbus; Configuring Alarm Outputs - GE Sievers Innovox Operation And Maintenance Manual

Toc analyzer
Hide thumbs Also See for Sievers Innovox:
Table of Contents

Advertisement

Chapter 6: Analyzer Operation
2.
For connection of the Analyzer to a network, select the straight-through Ethernet cable from the
Accessories Kit. Attach one end of the cable to the Ethernet port on the Analyzer, and plug the other end
into a convenient network port.
3.
Open a data acquisition program than can capture a TCP/IP transmitted .csv text file in real time.
Examples include PuTTY, HyperTerminal, and Tera Term.
N
:
The following Telnet port numbers are used to collect real-time data:
OTE
10802 - Historical Data (Data History or Cal/Ver History)
10801 - Real-Time Data (Generated during Measurements)

Using the Ethernet Connection and Modbus

To use Modbus, first ensure that the Ethernet cable is attached to the System/Controller board. Then follow the
procedure in
"Configuring the Analyzer's IP Address" on page
The InnovOx TOC Analyzer uses the standard Modbus port 502 for Ethernet communication. The Modbus map
for InnovOx is provided in

Configuring Alarm Outputs

The Analyzer has four binary alarm outputs, which can provide an alarm on any stream when the concentration
in that alarm exceeds a threshold value.
N
:
These alarms will only trigger relays on the I/O board and will not be indicated on the display. See
OTE
Install Input/Output, Cables, and Accessories" on page 79
To set the alarms
1.
Select the I/O tab.
2.
Press one of the alarm output buttons (such as the Alarm Output 1 button). The Alarm Output screen
appears.
GE Analytical Instruments ©2016
"Appendix D: Modbus Map."
156.
for I/O Board configuration information.
160 of 270
"Step 6:
DLM 68100-09 EN Rev. A

Advertisement

Table of Contents
loading

Table of Contents