Engineers Menu 3

View Network errors

This test routine allows the engineer to view the number
of data transmission errors for each network.
[ENT] to view :-
0
Network errors
Network 1 0000
Last error 2,05
1 8
-
to select network
0
to reset error counter
View Network Errors Flowchart

False Setting Routine

This option allows the engineer to set the system whilst
the premises are occupied. When selecting this option
the engineer can choose the following:
1.
The wards that will false set.
2.
The circuits that will remain active once the system
has been false set. Included circuits will remain
active during the false set and excluded circuits will
remain isolated during a false set. Normally all
circuit default to excluded.
3.
All outputs (digicom, bell, strobe etc.) can be
enable or disabled during the false set routine.
70
[
Error count
Last error
]
[ENT] to do
False setting
False set wards:
A,B,C,D,*,*,*,*
1 8
-
A C
/
Select test ccts
0001 Excluded
A C
/
circuits
All outputs will
remain active
0=SET WARDS
A=Next option
EXIT FOR WARDS:-
ABCD............
WARDS SET :-
ABCD............
Activate included circuits etc.
0
TESTING COMPLETE
[ESC] to quit.
False Setting Flowchart

Test Digicom channels

This test routine allows the engineer to test all eight
channels for the plug-on digicom.
[ENT] to test :-
Digicom channels
Channels active
1 * * * * * * *
1 8
-
Test Digicom Channels Flowchart
TS2500 Installation Manual
[
Setting wards
to toggle wards
to scroll wards A-H & I-P
[
B to toggle
to scroll through
[
B to toggle
[
0
to end test
]
[
Channel
*=off
to toggle channels
]