Pre Power-Up Checks; Initial Power-Up; Power-Up Checks; Relearn Required Message - Menvier Security TS2500 Installation & Programming Manual

1040 zone intruder alarm control system
Hide thumbs Also See for TS2500:
Table of Contents

Advertisement

TS2500 Installation Manual

Pre Power-Up Checks

Once the system is installed, but prior to powering-up
give the system one final check to ensure that:
1.
The wiring conforms to the requirements detailed in
this manual and that all connections are correct (A
to A, B to B etc.).
2.
All system cables are kept clear of mains supply
cables, telephone cables and R.F. cables. It is
recommended that cable ties are used to keep
cables separated.
3.
Verify that maximum cable lengths and resistance's
are not exceeded.
4.
Mains power supply cables to the system are
connected to an un-switched fused spur.
5.
Grommets are used where cables enter metal
housings to ensure that the cable insulation is not
compromised.

Initial Power-Up

To power the system for the first time:
1.
Place a small screwdriver blade between the pins
on the control panel PCB, marked "FACTORY
RESTART". This will ensure the factory default
parameters are set, see page 49 for a list of
defaults.
2.
Switch on the 230V mains supply and remove the
screwdriver blade after 5 seconds.
3.
Check that the power LED on the control panel PCB
is illuminated.
4.
Check that the remote keypads display "Panel Lid
tamper". The remote keypad sounders and
extension loudspeakers will operate.
5.
Enter the engineers passcode (default 1234) to
silence the sounders.
6.
Connect the standby battery.

Power-Up Checks

When the initial power-up checks have been
completed, check the following:
1.
Switch off the 240V mains supply and ensure that
the DC voltage at each device on each network is
greater than 11V whilst the system is powered from
its standby battery.
2.
Switch on the 240V mains supply and measure the
DC voltage between the mains earth connection
and AUX +12V. Then measure the DC voltage
between the mains earth connection and AUX 0V.
In both cases the measurement should be 1V or
less. If the voltage is greater than 1V, the system has
an "Earth Fault" and all cables should be checked
for isolation to Earth.
3.
Using a voltmeter measure the DC voltage across
the control panel PCB test points (V) and calculate
the system current consumption. Ensure that the
reading is not greater than 1.5A.
4.
Repeat test (3) with the system in an alarm condition
and ensure that the reading is not greater than
+
1.5A.
The TS2500 has an overload protection
circuit. If the power supply is overloaded, the
display will show: "PSU OVERLOAD ! ! !" and
sounder will sound.

Relearn Required Message

When the system is powered up after a factory restart,
the remote keypads will display "RELEARN REQUIRED".
On entering your engineer's passcode the system will
automatically select the "Confirm Network Devices"
option, see "Confirm Network Devices" on page 69.
After confirming the correct number of devices the
"RELEARN REQUIRED" message will be cleared. Once
cleared, entering your engineer's passcode will select
"Engineers menu 1".