TS2500 Installation Manual
On Test
Circuits with this attribute will be disabled from the
system for the period set by the "Test Time", see System
Timers. If the circuit is activated during this period the
activation will be logged and the user is informed of the
circuit failure when operating the system. The test fail
message can only be cleared with the Engineers
passcode. If at the end of the test period no activation's
have occurred the test attribute is automatically
removed. The test period is initiated by entering the
Engineers passcode.
Omittable
Circuits with this attribute can be omitted by the users.
Reset
This attribute is normally assigned to a circuit that is
connected to a vibration or smoke detector, so that
during the "Detector Reset" period the circuit is not
monitored.
Activity
Circuits with this attribute are monitored so that when
they activate the circuit activation is stored. When the
user attempts to set the system, any circuits not
activated during the "Activity Delay" period are
reported, indicating that the detector may be
obstructed. An example of this feature would be to
assign movement detectors within a warehouse area
with this attribute. This would report to the user at the time
of setting any detectors that have become obstructed
by pallets etc.
Entry
Circuits with this attribute will initiate the entry procedure
when the system is part-set and respond as normal
when full set. This attribute must be assigned to all
circuits that are required to initiate the entry procedure
in the part set condition.
Chime Tone 1
Circuits with this attribute will cause the internal sounders
and remote keypad sounders to generate a single
two-tone "chime" sound if the circuit is activated.
Chime Tone 2
Circuits with this attribute will cause the internal sounders
and remote keypad sounders to generate a double
two-tone "chime" sound if the circuit is activated.
Chime Tone 3
Circuits with this attribute will cause the internal sounders
and remote keypad sounders to generate a triple
two-tone "chime" sound if the circuit is activated.
Inverted
Circuits with this attribute are inverted so that a healthy
circuit is seen as active and an active circuit is seen as
healthy. This attribute should be used when monitoring
normally open devices such as exit terminator buttons
and pressure pads etc.
Shuntable
Circuits with this attribute are shunted (Isolated) when a
"Shunt Key" circuit is operated or when a "Shunt code" is
entered.
Beam Pair
Circuits with this attribute will only cause an alarm if two
or more circuits with the beam pair attribute are in alarm
in the same ward within the "Beam Pair" timer.
Eng. Test
Circuits with this attribute are enabled during the
engineer false setting routine.
Monitored
Circuits with this attribute activate the "Monitored"
output type when triggered.
Non Latching
This attribute is used to make the "Ward Key", "Shunt Key"
or "Security Key" non latching.

Circuit Wards

The TS2500 has sixteen wards which are labelled A to P,
each circuit can be assigned into one or more wards.
Circuits assigned to more than one ward will only be
armed when all the wards they are in are set.
Engineers menu 1
4
Program circuits
TS800 LEC 1
0001 Not used
Circuit No.
Enter circuit No. or
A C
/
B
=next network
[
to edit
B to paste last
- NO TEXT -
programmed
0001>Night
circuit details
A C
through circuit types
Circuit No.
0001 Night
Attribute Type
ACCESS
A C
through attributes
B
to toggle YES / NO
0001 is in wards
*,*,*,*,*,*,*,*
1-8
A C
/
wards A - H & wards I - P
Program Circuits Flowchart
Engineer's Menu 1
[
Location
Circuit Type
to scroll
Circuit Text
/
to scroll
[
Circuit type
YES or NO
NO
/
to scroll
[
= to toggle wards
to toggle between
[
41