Menvier Security TS2500 Installation & Programming Manual page 51

1040 zone intruder alarm control system
Hide thumbs Also See for TS2500:
Table of Contents

Advertisement

TS2500 Installation Manual
14
Modem on Com1 (Default)
The panel comms port (JP8) is used for the
modem.
Printer on Com1
The panel comms port (JP8) is used for the printer.
15
Chime Audible (Default)
Circuits that are programmed as chime will only
generate a chime tone.
Chime Visible
Circuits that are programmed as chime will
generate a chime tone and the remote keypads
will display the circuit that was triggered.
16
Manual Omits (Default)
Circuits with the omit attribute can only be omitted
via the user omit routine.
Automatic Omits
Circuits with the omit attribute are automatically
omitted if they are still active when the system is
being set.
17
Omit Tampers No (Default)
Tamper faults cannot be omitted by the user.
Omit Tampers Yes
Tamper faults can be omitted by the user.
18
O/M's mimic cct (Default)
The output modules connected to the control
panel indicate circuit mimic activations.
O/M's mimic alms
The output modules connected to the control
panel indicate circuit alarm activations.
19
Log Time & Date (Default)
The system log will show the time and date in the
following format: "17:10.57 25/12" where 25/12 is
the 25 December.
Log Time & Day
The system log will show the time and day in the
following format: "17:10.57 Wed 25" where Wed is
Wednesday and 25 is the date.
20
Global Setting (Default)
The user can set their allocated wards from any
remote keypad.
Local Setting
The user can only set their allocated wards from a
remote keypad assigned to their wards.
21
Global Unsetting (Default)
The user can unset their allocated wards from any
remote keypad.
Local Unsetting
The user can only unset their allocated wards from
a remote keypad assigned to their wards.
22
24hr Omit Global (Default)
Any 24hr circuit or group can be omitted from any
remote keypad.
24hr Omit Local
Only 24hr circuits or group that are assigned to the
same wards as the remote keypad can be
omitted.
23
Ward bell time (Default)
The system uses the respective "ward bell delay"
and "ward bell duration" timers when the system is
full or part set.
Global bell time
When the system is part-set the respective "ward
bell delay" and "ward bell duration" timers are
used. When the system is full set the system uses
the "global bell delay" and "global bell duration"
timers.
24
Latching Fire (Default)
Fire detection circuits will cause an alarm when
triggered and will only be re-armed after a full
reset, i.e. Enter passcode to silence alarm, then
enter passcode followed by [ESC] to reset the
alarm.
Nonlatching Fire
Fire detection circuits will cause an alarm when
triggered. On entering a passcode the alarm is
silenced, if the same circuit is activated before
carrying out a reset, the alarm re-triggered.
25
Online Printing (Default)
Events recorded in the system log are also sent to
the printer port.
Offline Printing
Events recorded in the system log are not sent to
the printer port.
26
Timed code o/p (Default)
The "User Code Accepted" output types are timed
for the duration of the "Access code time".
Latched code o/p
The "User Code Accepted" output types are
activated when user passcode is entered and
de-activated when the passcode is re-entered.
27
Activity flt ok (Default)
Users can set their wards with circuits flagged as
inactive.
Acitivity flt Bar
Users cannot set the system whilst circuits are
flagged as inactive (forced walk test).
Engineer's Menu 1
47