80010204-1d06xxxx • 80010701-0c01xxxx
2.
Replace the failing fan. (n = fan number)
80010204-1d06xxxx
Numeric sensor [NumericSensorElementName] going low (lower critical) has asserted. (Fan
6A/6B Tach)
Explanation: This message is for the use case when an implementation has detected a Lower Critical sensor going
low has asserted.
May also be shown as 800102041d06xxxx or 0x800102041d06xxxx
Severity: Error
Alert Category: Critical - Fan Failure
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0480
SNMP Trap ID: 11
Automatically notify Support: No
User response:
1.
Reseat the failing fan n, which is indicated by a lit LED near the fan connector on the system board.
2.
Replace the failing fan. (n = fan number)
80010701-0c01xxxx
Numeric sensor [NumericSensorElementName] going high (upper non-critical) has asserted.
(Ambient Temp)
Explanation: This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107010c01xxxx or 0x800107010c01xxxx
Severity: Warning
Alert Category: Warning - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0490
SNMP Trap ID: 12
Automatically notify Support: No
User response:
1.
Reduce the temperature.
2.
Check the server airflow. Make sure that nothing is blocking the air from coming into or preventing the air from
exiting the server.
386
IBM System x3550 M4 Type 7914: Installation and Service Guide