Panasonic FP Series Programming Manual page 1127

Hide thumbs Also See for FP Series:
Table of Contents

Advertisement

Analog unit instructions
Unit_AnalogOutput
_FP0_A04V
Description
This function block reads digital data from the FP0-A04 unit voltage output type from the output
channels 0–3 and stores the analog data in the input channels iOutChannel0–iOutChannel3. The
valid range is from -10–+10 V (-2000–+2000).
REFERENCE
For technical information, please refer to the manual FP0 Analog unit manual on your FPWIN Pro
installation CD.
see on page 1333
PLC types
The function block needs two PLC cycle scans to write all four channels into the
FP0-A04V Unit. Do not use pulse relay at EN input.
Wiring of analog outputs
OUTPUT
V0
COM
V1
COM
V2
COM
V3
COM
NC
A: Analog device
1126
Reads data from the FP0-A04 unit
A
A
A
A