Output wiring
Voltage output
V 0
I 0
COM
IN
V 1
I 1
V
I
OUT
COM
Connect output instrument between OUT/V and
OUT/COM terminal.
D/A conversion values
Voltage
output (V)
Current
output (mA)
Data types
Input variable
iIOWordOffset
iOutChannel
Output variable
iInChannel0–iInChannel1
Output
instrument
Value of WY
Digital value
-2000
0
0
2047
2000
4095
0
0
2000
2047
4000
4095
Data type
Function
The offset of the first WX/WY address of the RTD unit according
to its position.
FP0R, FP0, FP-Sigma: (use
ExpansionUnitToIOWordOffset_FP0 (see page 1128)) or
unit 1 => address 2, unit 2 => address 4, unit 3 => address 6
FP-X: (use ExpansionUnotToIOWordOffset_FPX_FP0 (see page
1129)) or
FP0 adapter
1st unit
2nd unit
INT
3rd unit
4th unit
5th unit
6th unit
7th unit
8th unit
Output value channel
-20002–000->-10V–10V.
0–4000->4mA-20mA
Input value at corresponding output channel 0–1
INT
0V–5V, 0mA–20mA -> 0–4000.
-10V–10V, -100mV–100mV -> -2000–2000
Current output
V 0
I 0
COM
IN
V 1
I 1
V
I
OUT
COM
Connect output instrument between OUT/I and
OUT/COM terminal.
Analog output
-10 V
0 V
+10 V
0 mA
10 mA
20 mA
address of
address of
unit 1
unit 2
30
32
40
42
50
52
60
62
70
72
80
82
90
92
100
102
Analog unit instructions
Output
instrument
address of
unit 3
34
44
54
64
72
84
94
104
1095