Panasonic FP Series Programming Manual page 1118

Hide thumbs Also See for FP Series:
Table of Contents

Advertisement

Data types
Input variable
iIOWordOffset
Output variable
iChannel0–iChannel7
In this example the function has been programmed in ladder diagram (LD) and structured text
Example
(ST).The same POU header is used for all programming languages.
POU header
All input and output variables used for programming this function have been declared in the POU
header.
Body
Use ExpansionUnitNumberToIOWordOffset_FP0 (see page 1125) to calculate the word offset of
the analog unit connected to an FP0.
This function block reads the analog input data from the FP0-TC4 (TC8) unit and stores the digital
values in the corresponding ínput channels:
Range
K, J Type
T Type
R Type
8000
Data type
Function
The offset of the first WX/WY address of the RTD unit according
to its position.
FP0R, FP0, FP-Sigma: (use
ExpansionUnitToIOWordOffset_FP0 (see page 1128)) or
unit 1 => address 2, unit 2 => address 4, unit 3 => address 6
FP-X: (use ExpansionUnotToIOWordOffset_FPX_FP0 (see page
1129)) or
INT
input values on the corresponding output channel (0–3 for
FP0-TC4, channel0–7 for FP0-TC8):
Range K, J type (-100,1°C to 500,1°C->-1001 to 5001 or
-148,1°F to 790,1°F -> -1481 to 7901)
Range T type: (-100,1°C to 400,1°C -> -1001 to 4001 or -148,1°F
to 752,1°F -> -1481 to 7521)
Range R type: (0°C to 1500,1°C -> 0 to 15001 or 32°F to
1590,1°F -> 320 to 15901)
8000 (when the thermocouple is broken)
°C values
digital values
-100.1–500.1
-1001–5001
-100.1–400.1
-1001–4001
0–1500.1
0–15001
when the thermocouple is broken
FP0 adapter
address of
address of
unit 1
unit 2
1st unit
30
2nd unit
40
3rd unit
50
4th unit
60
5th unit
70
6th unit
80
7th unit
90
8th unit
100
°F values
-148.1–790.1
-148.1–752.1
32–1590.1
Analog unit instructions
address of
unit 3
32
34
42
44
52
54
62
64
72
72
82
84
92
94
102
104
digital values
-1481–7901
-1481–7521
320–15901
1117