Alcatel-Lucent 1643 AMS Operation Manual page 318

Access multiplexer and access multiplexer small (formerly metropolis am and metropolis ams. release 1.0 through 7.2. alarm messages and trouble clearing guide
Hide thumbs Also See for 1643 AMS:
Table of Contents

Advertisement

Alarm messages
VC-4 Unequipped
...................................................................................................................................................................................................................................
Alarm identifier
Information
Alarm category
ASAP
Alarm severity
(default setting)
Reporting state
(default setting)
Local indications
Cause
Actions
Note(s)
...................................................................................................................................................................................................................................
1-298
VC4cUNEQ
VC-4 in STM-1 signal not in use.
Transmission
sdhHOPath
Prompt
Reported
Cross-connection not consistently defined at both sides (for example, at local
and remote station) of a line section.
Define or change the cross-connection at the other side consistently with the
local side.
When defining or changing a cross-connection this alarm will almost inevitably
come up as it is practically impossible to issue the changes at both sides at the
same moment.
Alcatel-Lucent - Proprietary
See notice on first page
365-312-803R7.2
Issue 4, May 2007