Technical data
13.8 Option modules
13.8.8.2

Construction for external position detection system

Construction
How does it work?
● Range of stroke (linear actuator)
● Angle of rotation (part-turn actuator)
Mounting method
● On the linear actuator
● On the part-turn actuator
Material
● Enclosure
Weight, basic device
Torque for cable gland nut made of plastic
13.8.8.3

Certificates, approvals, explosion protection for external position detection system

Electrical data
For connecting to circuits with the following
peak values
Certificates and approvals
CE conformity
Explosion protection
Explosion protection in accordance with
Intrinsic safety "ia"
Intrinsic safety "ic"
298
3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the posi‐
tioner shaft 16 to 90°)
30 ... 100°
Using mounting kit 6DR4004-8V and, where necessary, an
additional lever arm 6DR4004-8L on actuators according to
IEC 60534-6-1 (NAMUR) with a fin, columns, or a plane
surface.
Using mounting kit 6DR4004-8D on actuators with mount‐
ing plane according to VDI/VDE 3845 and IEC 60534-6-2:
The required mount must be provided on the actuator-side.
Makrolon® glass-fiber reinforced polycarbonate (PC)
Approximately 0.9 kg (1.98 lb)
2.5 Nm
U
= 5 V
i
I
= 100 mA
i
P
= 160 mW
i
C
= negligibly small
i
L
= negligibly small
i
The applicable directives and applied standards with their revision levels can
be found in the EC declaration of conformity on the Internet.
Ex markings
ATEX
Zone 1:
II 2 G Ex ia IIC T6/T4 Gb
Zone 21:
II 2 D Ex ia IIIC T110°C Db
Zone 2:
II 3 G Ex ic IIC T6/T4 Gc
SIPART PS2 with PROFIBUS PA