Initializing the linear actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
2. Call the "2.YAGL" parameter. To do this, briefly press the
3. Check whether the value displayed in the "2.YAGL" parameter matches the setting of the
4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of parameter
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
The display shows the following:
on the display depending on the setting:
transmission ratio selector. If required, change the setting of the transmission ratio selector
to 33° or 90°.
3 is optional. The display shows the determined total stroke only at the end of the
initialization phase.
– Briefly press the
mm. You are then directed to parameter 4.
– Call the "3.YWAY" parameter. To do this, briefly press the
the following:
Note
Set the "3.YWAY" parameter
Proceed as follows to set parameter 3:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter with the buttons or to the read value.
button if you do not require any information about the total stroke in
Commissioning
7.5 Commissioning linear actuators
. The settings
button for at least 5 seconds.
button. The following is shown
button. The display shows