P5.LEVL3 - threshold 3
Possible settings:
Purpose:
Factory setting:
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
0.1 ... 100.0
Use this sub-parameter to set threshold 3 for the maximum deviation
of the current average value of position from the average value of
reference. The value is given in percent. Set the threshold in a range
from '0.1' to '100.0'.
The positioner triggers a message if the difference between the
average value of position and the average value of reference ex‐
ceeds threshold 3. The procedure to activate and display this mes‐
sage is described in the 'XDIAG' parameter.
10.0
Parameter assignment
9.3 Description of parameters
197