Byt
Bit
No.
Diagnostics events
e
2
0
65
Limit 2 for path integral
(100% strokes) excee‐
ded
1
66
Limit 3 for path integral
(100% strokes) excee‐
ded
2
67
Limit 1 for changes in di‐
rection exceeded
3
68
Limit 2 for changes of di‐
rection exceeded
4
69
Limit 3 for changes of di‐
rection exceeded
5
70
Limit 1 for position aver‐
age exceeded
6
71
Limit 2 for position aver‐
age exceeded
7
72
Limit 3 for position aver‐
age exceeded
3
0
73
PST reference time ex‐
ceeded (limit 1)
1
74
PST reference time ex‐
ceeded (limit 2)
2
75
PST reference time ex‐
ceeded (limit 3)
76 ...
Reserved
80
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
Effect of the event
Quality status code
Good, maintenance de‐
mand
Uncertain, maintenance
demand
Good, maintenance re‐
quirement
Good, maintenance de‐
mand
Uncertain, maintenance
demand
Good, maintenance re‐
quirement
Good, maintenance de‐
mand
Uncertain, maintenance
demand
Good, maintenance re‐
quirement
Good, maintenance de‐
mand
Uncertain, maintenance
demand
-
Functions/operations using PROFIBUS PA
10.3 Cyclic data transfer
1)
DIAGNOSTICS bit
DIA_MAINTENANCE_DEMAN‐
DED
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE
DIA_MAINTENANCE_DEMAN‐
DED
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE
DIA_MAINTENANCE_DEMAN‐
DED
DIA_MAINTENANCE_ALARM
DIA_MAINTENANCE
DIA_MAINTENANCE_DEMAN‐
DED
DIA_MAINTENANCE_ALARM
-
Group
M12
M
M1
M12
M
M1, P
M12, P
M, P
M1
M12
M
-