Setting the actuator
1. The positioner is in the "P manual mode". The current potentiometer voltage P in percent
2. Check whether the mechanical unit can be moved freely in the entire travel range. Move
3. After checking, move the actuator to a central position. This accelerates the initialization
See also
External position detection (Page 53)
7.6.2

Automatic initialization of part-turn actuators

Requirements
The following conditions must be fulfilled before activating the automatic initialization:
1. The travel range of the actuator can be passed through completely.
2. The actuator shaft is at a central position.
Initializing the part-turn actuator automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press
configured until then are retained.
All parameters are reset to factory settings only if you have explicitly activated the preset
settings in the "PRST" parameter.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
is shown on the upper line in the display. "NOINI" blinks in the lower line of the display.
Examples of corresponding displays are given below:
the drive to the respective end position for this purpose using the
Note
End position
By simultaneously pressing the
process.
7.6 Commissioning part-turn actuators
and
buttons, you reach the end position faster.
Commissioning
or
button.
. The settings
131