Pneumatic Data; Construction - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Technical data

13.3 Construction

13.2

Pneumatic data

Pneumatic data
Auxiliary power (air supply)
● Pressure
1)
Air quality to ISO 8573-1
● Solid particulate size and density
● Pressure dew point
● Oil content
Unrestricted flow (DIN 1945)
● Inlet air valve (ventilate actuator)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
● Exhaust valve (deaerate actuator for all versions except fail
in place)
2)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
● Exhaust valve (deaerate actuator for fail in place version)
2 bar (29 psi)
4 bar (58 psi)
6 bar (87 psi)
Valve leakage
Throttle ratio
Auxiliary power consumption in the controlled state
Sound pressure level
The following applies to fail in place: 3 ... 7 bar (43.5 to 101.5 psi)
1)
When using device versions Ex d (6DR5..5-... and 6DR5..6-...), values are reduced by approximately 20%.
2)
13.3
Construction
Construction
How does it work?
● Range of stroke (linear actuator)
● Angle of rotation (part-turn actuator)
Mounting method
284
2)
Compressed air, carbon dioxide (CO2), nitrogen (N), noble
gases or cleaned natural gas
1.4 ... 7 bar (20.3 to 101.5 psi)
Class 2
Class 2 (min. 20 K (36°F) below ambient temperature)
Class 2
4.1 Nm³/h (18.1 USgpm)
7.1 Nm³/h (31.3 USgpm)
9.8 Nm³/h (43.1 USgpm)
8.2 Nm³/h (36.1 USgpm)
13.7 Nm³/h (60.3 USgpm)
19.2 Nm³/h (84.5 USgpm)
4.3 Nm³/h (19.0 USgpm)
7.3 Nm³/h (32.2 USgpm)
9.8 Nm³/h (43.3 USgpm)
< 6⋅10
Nm³/h (0.0026 USgpm)
-4
Adjustable up to ∞: 1
< 3.6⋅10
Nm³/h (0.158 USgpm)
-2
L
< 75 dB
A eq
L
< 80 dB
A max
3 ... 130 mm (0.12 ... 5.12") (angle of rotation of the posi‐
tioner shaft 16 ... 90°)
30 ... 100°
Operating Instructions, 02/2016, A5E00127926-AB
SIPART PS2 with PROFIBUS PA