Definition Of The Status; Sub-Status For Deactivated Condensed Status - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Functions/operations using PROFIBUS PA
10.3 Cyclic data transfer
Byte
Bit
Name and meaning
3
0
Reserved
... 6
7
EXTENSION_AVAILABLE
Extension available
10.3.3.3

Definition of the status

Status byte
The status is used to provide information about the quality of the input and output values. This
information is classified into four stages. Quality stages such as "Bad", "Uncertain", "Good"
and "Good (cascade)" are accompanied with further information. In this case, it deals with the
sub-status and the limit bits. The status byte has the following structure:
Quality
Limit bits
The meaning of the sub-status depends on whether the condensed status is activated or not.
The sub-status is therefore specified separately for both the cases.
10.3.3.4

Sub-status for deactivated condensed status

Bit
7
6
5
4
3
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
0
0
0
1
0
236
7
6
Quality
2
1
0
0
x
x
Bad, non specific
1
x
x
Bad, configuration error
0
x
x
Bad, not connected
1
x
x
Bad, device failure
0
x
x
Bad, sensor failure
Cause
-
Further information about the trig‐
gering diagnosis event is availa‐
ble in DIAGNOSIS_EXTENSION
and DIAGNOSIS_EXTEN‐
SION_2.
Status byte structure
5
4
Sub-status
00
Bad
01
Uncertain
10
Good
11
Good (cascade)
00
Good
01
Lower limit reached
10
Upper limit reached
11
Value is constant.
Name profile
Measures
-
-
3
2
German name
Schlecht
Schlecht, Konfigurationsfehler
Schlecht, keine Verbindung
Schlecht, Gerätefehler
Schlecht, Sensorfehler
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB