8.5
Safety characteristics
The safety characteristics necessary for use of the system are listed in the SIL declaration of
conformity. These values apply under the following conditions:
● The positioner is only used in applications with low demand rate for the "Low demand mode".
● "Jumper" on the basic electronic system was plugged into the left position facing the
● The positioner is blocked against unwanted and unauthorized changes/operation.
● The shut-off signal for the positioner is generated at the input for the safety shutdown
● The connected actuator must be singe-acting and return the valve to the safe end position
● The air outlet does not contain any additional cross-sectional contractions leading to an
● The restrictor in the Y1 circuit may not be completely closed during operation.
● The auxiliary pneumatic power is free of oil, water and dirt in line with:
● The average temperature viewed over a long period is 40 °C.
● Fault rates are calculated on the basis of a mean time to repair (MTTR) of 8 hours.
● In case of a fault, the pneumatic outlet of the positioner is depressurized. A spring in the
● A dangerous failure of the positioner is when the pressure outlet is not depressurized, or
See also
Settings (Page 142)
8.6
Maintenance/check
Interval
We recommend that the functioning of the positioner is checked at regular intervals of one
year.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
terminals at position "Shut Down enabled" or removed completely.
(terminals 81 and 82) by a safe system which meets at least SIL 2. The LOW level has a
maximum of 4.5 V at the input terminals.
by spring force in the following scenario:
– At a chamber pressure (Y1 connection) up to a third of the maximum available intake
pressure (P
connection)
z
increased dynamic pressure. In particular, a silencer is only allowed if icing or other
contamination is ruled out.
DIN/ISO 8573-1, maximum class 2
pneumatic actuator must move the valve to the pre-defined, safe end position.
the safety position is not reached, with a LOW level of maximum 4.5 V at the input for the
safety shutdown.
Functional safety
8.6 Maintenance/check