When operating the positioner with natural gas, you must follow and adhere to the following
safety notes:
Operation with natural gas
1. Only positioners and option modules which are connected to power supplies with type of
2. Do not operate the positioner with natural gas in closed spaces.
3. Natural gas is continuously blown off in the servo-drive depending on the model. Special
4. The mechanical limit switch module must not be used when operating the positioner with
5. Depressurize the devices operated with natural gas adequately during maintenance
Note
Quality of natural gas
Only use natural gas which is clean, dry and free from additives.
7.2

Overview

Note
● During the initialization process, the operating pressure must be at least one bar more than
General information about commissioning
1. After installing the positioner on a pneumatic actuator, you must supply electric and
2. The positioner is in the "P manual mode" before initialization. At the same time, "NOINI"
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
WARNING
protection "Intrinsic safety, protection level [ia]" may be operated with natural gas.
care must therefore be taken during maintenance activities near the positioner. Always
ensure that the immediate surroundings of the positioner are adequately ventilated.
The maximum values for ventilation are listed in section "Technical data for natural gas
as actuator medium (Page 290)".
natural gas.
activities. Open the cover in an explosion-free atmosphere and depressurize the device
for at least two minutes.
that required to close or open the valve. However, the operating pressure should not be
greater than the maximum permissible operating pressure for the actuator.
pneumatic auxiliary power to it.
blinks in the lower line of the display.
Commissioning
7.2 Overview
115