Siemens SIPART PS2 Operating Instructions Manual page 74

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Installing/mounting
4.7 Installing the optional modules
Procedure for installing the EMC filter module
Figure 4-17
1. You have performed the steps described in the section "General information about the
2. Unplug the ribbon cable connector
3. Remove the basic electronics
4. Loosen the screw
5. Insert the connector of the ribbon cable (A) into the slot as shown below.
6. Secure the EMC filter module using the screw
7. Fit the basic electronics
8. Insert the ribbon cable connector
74
EMC filter module terminals
Positioner
Yellow wheel for locking the position detection
Ribbon cable connector of fitted potentiometer,
or ribbon cable connector of EMC filter module
Installation EMC filter module
installation of option modules (Page 54)".
.
that fix the basic electronics to the pneumatic block.
in the connection area of the positioner.
Note: There is no space for the ribbon cable (A) in earlier versions of the positioner. Here
you fasten the ribbon cable with the supplied cable tie at the container.
electronics.
to the fitted potentiometer from the basic electronics
from the positioner. To this end, remove the two screws
back into the positioner.
of the EMC filter module onto the positioner basic
Basic electronics
Screw
EMC filter module C73451-A430-D23
loosened in the fourth step.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB

Advertisement

Table of Contents
loading

Table of Contents