Siemens SIPART PS2 Operating Instructions Manual page 184

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment
9.3 Description of parameters
d1.LIMIT - limit for slipstick detection
Adjustment range:
Purpose:
Factory setting:
d2.FACT1 - Factor 1
Adjustment range:
Purpose:
Factory setting:
d3.FACT2 - Factor 2
Adjustment range:
Purpose:
Factory setting:
d4.FACT3 - Factor 3
Adjustment range:
Purpose:
Factory setting:
See also
Diagnostic value '15.DEVI - General control valve fault' (Page 259)
184
0.1 ... 100.0
Use this sub-parameter to set the base limit for slipstick detection
in percent. Set the base limit in a range from '0.1' to '100.0'.
1.0
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold
1. Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of the values entered for 'd1.LIMIT' and 'd2.FACT1'.
The threshold 1 message is displayed when threshold 1 is excee‐
ded. The process to activate and display this message is described
in the 'XDIAG' parameter.
2.0
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold
2. Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of the values entered for 'd1.LIMIT' and 'd3.FACT2'.
The threshold 2 message is displayed when threshold 2 is excee‐
ded. The process to activate and display this message is described
in the 'XDIAG' parameter.
5.0
0.1 ... 100.0
Use this sub-parameter to set the factor for formation of threshold
3. Set the factor in a range from '0.1' to '100.0'. The threshold is the
product of the values entered for 'd1.LIMIT' and 'd4.FACT3'.
The threshold 3 message is displayed when threshold 3 is excee‐
ded. The process to activate and display this message is described
in the 'XDIAG' parameter.
10.0