Electrical Wiring; Bus Cable - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Connect

5.2 Electrical wiring

If the 24-V signal is interrupted, the safety position is set as described in chapter "Pneumatic
connection (Page 101)".
Communication with the master is still possible. The "Jumper" on the basic electronics is used
to activate this function. It can be accessed after removing the module cover, and must be
switched from the right position (delivery state) to the left position.
5.2
Electrical wiring
5.2.1

Bus cable

The following image will help you in preparing the bus cable for the connection:
a
Figure 5-2
Devices without flameproof enclosure are:
● Normal version of devices
● Intrinsically safe versions
● Versions for zones 2 and 22
82
80 mm: Normal version of device
120 mm: Version with flameproof enclosure (6DR5..5)
Bus cables to be used:
SIMATIC NET, PB FC Process Cable, bus cable for IEC 61158-2
Cable shield
Preparation of bus cable
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB