Description Of Parameters; Initialization Parameters 1 To 5; Yfct' Type Of Actuator - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Parameter assignment

9.3 Description of parameters

9.3
Description of parameters
9.3.1

Initialization parameters 1 to 5

9.3.1.1

'1.YFCT' Type of actuator

Requirement:
Possible settings:
Purpose:
Description:
154
Type of actuator as well as mounting type and direction of action
are known.
Actuator with normal direction of
action
● turn
● WAY
● FWAY
● LWAY
● ncSt
● ncSL
● ncSLL
Use this parameter to adjust the positioner to the respective actua‐
tor.
● turn/-turn: Use this setting for a part-turn actuator with a directly
mounted positioner.
● WAY/-WAY: Use this setting for a linear actuator with a carrier
pin mounted on the lever.
● FWAY/-FWAY: Use this setting for a linear actuator with a carrier
pin mounted on the actuator spindle.
● LWAY/-LWAY: Use this setting for an external linear
potentiometer on a linear actuator.
● ncSt/-ncSt: Use this setting for an NCS sensor (6DR4004-.N.10
and -.N.40) on a part-time actuator.
● ncSL/-ncSL: Use this setting for an NCS sensor (6DR4004-.N.
20) on a linear actuator for strokes < 14 mm (0.55 inch).
● ncSLL/-ncLL: Use this setting for an NCS sensor (6DR4004-.N.
30) on a linear actuator for strokes > 14 mm (0.55 inch) and for
an internal NCS module. No limitations apply to the internal NCS
module.
In the case of actuators with inverted direction of action, use the
settings with the minus sign, e.g. -turn.
Meaning of actuator with normal direction of action:
● Part-turn actuator closes when the drive shaft, positioner shaft
or magnet of the NCS sensor rotates in the clockwise direction.
● Linear actuator closes when the actuator spindle rotates
downwards and the positioner shaft or magnet of the NCS sensor
rotates in the anti-clockwise direction.
Actuator with inverted direction of
action
● -turn
● -WAY
● -FWAY
● -LWAY
● -ncSt
● -ncSL
● -ncLL
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB

Advertisement

Table of Contents
loading

Table of Contents