Remedial Measures Table 5 - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Alarm, fault and system messages
11.4 Fault correction
See also
Cleaning of the screens (Page 278)
11.4.6

Remedial measures table 5

Fault profile (symptoms)
● Zero point displaces sporadically
(> 3%).
● The device function has completely
failed: No representation on the
display either.
Fault table 5
See also
Repair/Upgrading (Page 280)
276
Possible cause(s)
● Impact or shock loads result in
accelerations so high that the friction
clutch moves, e.g. due to "vapor
shocks" in vapor lines.
● Electrical auxiliary power supply is
not adequate.
● In case of very high continuous
loads due to vibrations (oscillations):
● Screws of the electrical connecting
terminals may be loosened.
● Electrical connecting terminals and/
or electronic components may be
knocked out.
Corrective measures
● Rectify the causes for shock loads.
● Re-initialize the position controller.
● Check the electrical auxiliary power
supply.
● Tighten the screws firmly and secure
using sealing wax.
● Repair
● For prevention: Install the positioner
on the damping pads.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB