Rated signal range
Dynamic range
Auxiliary voltage U
H
External load R
[kΩ]
B
Transmission error
Temperature influence
Resolution
Residual ripple
For connecting to circuits with the fol‐
lowing peak values
Effective internal capacitance
Effective internal inductance
Galvanic isolation
Test voltage
13.8.3

SIA module

SIA module
Limit encoder with slotted initiators
and fault message output
2 slotted initiators
● Binary output (limit transmitter) A1: Terminals 41 and 42
● Binary output (limit transmitter) A2: Terminals 51 and 52
● Connection
● Signal state High
(not triggered)
● Signal state Low (triggered)
● 2 slotted initiators
● Function
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
Without explosion protec‐
tion or suitable for use in
the SIPART PS2 Ex d
+12 ... +35 V
-
-
Safe galvanic isolation from alarm option and basic device
Without Ex protection
6DR4004-8G
2 wire technology in accordance with EN 60947-5-6 (NAMUR), for switching amplifi‐
With Ex protection Ex ia
(only in temperature class
T4)
4 ... 20 mA, short-circuit proof
3.6 ... 20.5 mA
+12 ... +30 V
≤ (U
[V] - 12 V)/I [mA]
H
≤ 0.3 %
≤ 0.1%/10 K (≤ 0.1%/18 °F)
≤ 0.1 %
≤ 1 %
U
= DC 30 V
i
I
= 100 mA
i
P
= 1 W
i
C
= 11 nF
i
L
= negligibly small
i
DC 840 V, 1 s
With Ex protection Ex "ia"
6DR4004-6G
ers connected on load side
> 2.1 mA
< 1.2 mA
Type SJ2-SN
NC contact (NC, normally closed)
Technical data
13.8 Option modules
With Ex protection
Ex "ic", "nA", "t"
+12 ... +30 V
"ic":
U
= DC 30 V
i
I
= 100 mA
i
"nA"/"t":
U
≤ DC 30 V
n
I
≤ 100 mA
n
P
≤ 1 W
n
C
= 11 nF
i
L
= negligibly small
i
With Ex protection Ex "ic",
"nA", "t"
6DR4004-6G
293