System Messages During Initialization - Siemens SIPART PS2 Operating Instructions Manual

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

See also
Display (Page 103)
11.1.3

System messages during initialization

Remarks about the tables:
nn
/
Messages during initialization
Message
Line
Up
Down
P---
X
RUN1
X
RUN2
X
RUN3
X
RUN4
X
RUN5
X
YEND1
X
YEND2
X
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
Stands for variable numeric values
Error symbol
(slash): the texts on the left and right of the slash flash alternately
Meaning/cause
Measuring range was exceeded, the potenti‐
ometer is in the inactive zone, the transmis‐
sion ratio selectors or the effective lever arm
are not adjusted as per the actuator travel
Initialization was started, part 1 is active (the
direction of action is determined)
Initialization part 2 is active (actuator travel
check and determination of endstops)
Initialization part 3 is active (determination
and display of travel times)
Initialization part 4 is active (determination of
the minimum controller increment length)
Initialization part 5 is active (optimization of
the transient response)
The first end position can be approached only
in case of a manual initialization
The second end position can be approached
only in case of a manual initialization
Alarm, fault and system messages
11.1 Output of system messages in the display
Measure
● Switch the transmission ratio selector to
90°, especially in the case of part-turn
actuators.
● Adjust the effective lever length of linear
actuators as per the measuring range.
● Wait.
● Wait.
● Wait.
● Wait.
● Wait until "FINSH" is displayed.
Initialization was completed successfully.
1. Approach first end position using
key.
2. Acknowledge using
1. Approach second end position using
or
key.
2. Acknowledge using
or
key.
key.
247