Advertisement

9.3.3.5

Monitoring the deadband 'E.\\DEBA'

E. DEBA - Monitoring the deadband
Requirement:
Possible settings:
Purpose:
Factory setting:
E1.LEVL3 - Deadband threshold
Adjustment range:
Purpose:
Factory setting:
Note
Fault message display
The three-stage alarm display has not been implemented for monitoring of the deadband. The
positioner triggers only threshold 3 fault messages depending on the setting.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
The '50.XDIAG' Activation of extended diagnostics (Page 170) pa‐
rameter is set to 'On1', 'On2' or 'On3'.
The '31.DEBA' Deadband of controller (Page 160) parameter is set
to 'Auto'.
● OFF
● On
Use this parameter to continuously monitor the automatic adaptation
of the deadband. Monitoring is performed in three steps. To activate
monitoring, set the parameter to 'On'. The sub-parameter is dis‐
played. Appropriately set the sub-parameter.
The current value is displayed in Diagnostic value '26.DBUP - Dead‐
band UP' / '27.DBDN - Deadband DOWN' (Page 263). The position‐
er triggers a message if the current value exceeds the threshold.
OFF
0.1 ... 2.9
Use this sub-parameter to set the threshold to the deadband in per‐
cent. Set the threshold in a range from '0.1' to '2.9'.
The threshold 3 fault message is displayed when the current dead‐
band exceeds the threshold during the test. The procedure to acti‐
vate and display this error message is described in the 'XDIAG' pa‐
rameter.
2.0
Parameter assignment
9.3 Description of parameters
185