Commissioning
7.5 Commissioning linear actuators
4. Set the "3.YWAY" parameter to determine the total stroke in mm. The setting of the
5. Call the "5.INITM" parameter. To do this, press the
6. Start the initialization process. To do this, press the
7. Determine the lower endstop of the actuator spindle.
8. Move the actuator to the desired position using the
128
"3.YWAY" parameter is optional. The display shows the determined total stroke only at the
end of the initialization phase.
– Briefly press the
mm. You are then directed to parameter 4.
– Call the "3.YWAY" parameter. To do this, briefly press the
the following:
Note
Set the "3.YWAY" parameter
To set the "3.YWAY" parameter proceed as follows:
1. On the scale of the lever, read the value marked by the carrier pin.
2. Set the parameter to the read value with the
following:
the display shows the following:
The current potentiometer position is output on the display after 5 seconds. Examples of
the displayed potentiometer positions are given below:
button if you do not require any information about the total stroke in
button. The display shows
or
button.
button twice. The display shows the
button for at least 5 seconds until
or
button.
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB