1.5.6.3 S2 = 2:
To control I-acting motorized actuating drives.
In S-controllers with external feedback the "internal position control circuit" is replaced by a real
position controller (with the K-controller output y as a setpoint and the position feedback y
FE6 as an actual value). As a result a manipulated variable limiting of ya and an absolute value
preset of y
and ys are now possible.
E
With the absolute value preset of y
able via the SES as an absolute value y
low-up input y
(FE5), the freely connectable input range (S4=1) must be used because in the
N
permanently connected input range, FE5 is not available at S2=2 (see fig. 1--14).
Here too the response threshold of the position controller is preset with the parameters tE (mini-
mum turn-on duration) and tA (minimum turn-off duration) in connection with tY (floating time).
-- Switching on
A
-- Switching off
A
-- Hysteresis
A
-- Pause
A
If a control deviation of xds ≥ A
dently to continuous contact. xds is reduced by the negative follow-up of the position control
circuit until xds <A
ea
time tA pulse of length tE are output with subsequent pause time tA until xds ≤A
+Δy
-Aea-Aee
Aea Aee
-Δy
These single pulses are also output if xds coming from zero does not reach A
pulses which are not fully transformed into the path change (rotational movement) additionally
calm the control circuit, i.e. in theory (without lag) the single pulses would switch off at 0.25 or
0.5 A
. The opposite direction can only occur at appropriate control deviation after the pause
ee
time tA.
The control difference of the position control circuit xds can be measured at assigmment to an
analog output.
Manual adjustment via the front panel is made at S67=2 here too as an incremental adjustment
by overmodulating the three-position switch so that manual adjustment is possible even when
the position feedback is interrupted.
To simplify commissioning of the position control circuit, the manual manipulated variable is
preset absolutely at S67=0 (manipulated variable of the K-controller) so that the setpoint of the
position control circuit is changed continuously in this structure switch position to enable
optimization (see chapter 4.3). It should be taken into account here that the manual
SIPART DR22 6DR2210
C79000-G7476-C154-03

Three-position step (S) -- controller with external feedback

it is also possible to preset the manual manipulated vari-
E
in follow-up operation. If y
ES
100 % ⋅ tE
= 4
ee
tY
100 % ⋅ tE
= 3
ea
tY
100 % ⋅ tE
-- A
=
ee
ea
tY
100 % ⋅ tA
=
a
tY
is set up, the three-position switch switches direction-depen-
ee
is reached. The continuous contact is now switched off. After the pause
xdS
1 Technical Description
1.5 Functional description of the structure switches
1.5.6 Controller output structures (S2, S61 to S68)
is preset via the fol-
E
via
R
is reached.
ee
. These single
ee
107