Siemens SIPART PS2 Operating Instructions Manual page 238

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

Functions/operations using PROFIBUS PA
10.3 Cyclic data transfer
DIAGNOSTICS_EXTENSION physical block parameter
Byte
Bit
No.
0
0
1
1
2
2
3
3
4
4
5
5
6
7 ... 21
2
5
22
6
23
7
24
3
0
25
1
26
3
27
3
28
4
29
5
30
6
31
7
32
33 ... 48
238
Diagnostics events
Run time error of the actuator
The device is not in the "Auto‐
matic mode"
Binary 1 is active (only mes‐
sage)
Action triggered by binary input
1
Binary 2 is active (only mes‐
sage)
Action triggered by binary input
2
Reserved
Limit for alarm A1 exceeded
Limit for alarm A2 exceeded
Error in the device electronic
unit
The device is not yet ready for
operation (not initialized)
The device is not yet ready for
operation (initialization error)
Reserved
Reserved
Device in the Manual mode (FB
in the Manual mode)
Device in the Simulation mode
(FEEDBACK is simulated)
Device in the TRACE mode
Diagnostics simulation (diag‐
nostics events are simulated)
Reserved
Hard-coded effect of a diagnostics event
Quality status code
Bad, maintenance requirement DIA_SUPPLY
Uncertain, simulation value
Good, maintenance required
Uncertain, simulation value
Good, maintenance required
Uncertain, simulation value
-
Good, maintenance required
Good, maintenance required
Bad, device error
Bad, configuration error
Bad, configuration error
-
-
Depends on the set status
Depends on the simulated sta‐
tus
-
Depends on the simulated di‐
agnostics event
-
Operating Instructions, 02/2016, A5E00127926-AB
DIAGNOSTICS bit
None
DIA_MAINTENANCE
None
DIA_MAINTENANCE
None
-
DIA_MAINTENANCE
DIA_MAINTENANCE
DIA_MEM_CHKSUM
DIA_NOT_INIT
DIA_INIT_ERR
-
-
None
None
None
Depends on the simulated di‐
agnostics event
-
SIPART PS2 with PROFIBUS PA