Commissioning

7.7 Device replacement

7.7
Device replacement
Introduction
Note
Initialization
The positioner can be replaced without having to interrupt ongoing processes. However,
copying and pasting of the initialization parameters only allows an approximate adjustment of
the positioner to your actuator. Following initialization, the positioner initially works with the
manually defined parameters.
● For this reason, an automatic or manual initialization should be carried out as soon as
Note
Deferred initialization
Initialize the new positioner as soon as possible. The following properties can be ensured only
after initializing:
● Optimum adjustment of the positioner as per the mechanical and dynamic properties of the
● Non-deviating position of end stops
● Correctness of the maintenance data
There are two ways of replacing a positioner when the equipment is in operation, without having
to interrupt the process. The two options depend on whether your positioner has
communication.
First possibility - with communication
1. Read the initialization parameters from the previous positioner. Use the parameter
2. Read the initialization parameters from Point 1 into the new positioner.
3. Fix the actuator at its current position mechanically or pneumatically. Use the locking
4. Determine the actual position value. To do this, read the actual position value from the
5. Dismount the previous positioner from the actuator.
6. Attach the lever arm of the previous positioner to the new positioner.
7. Mount the new positioner on the actuator.
8. Set the transmission ratio selector of the new positioner to the same position as that of the
9. If the displayed actual position value differs from the noted value, correct the deviation by
136
possible.
actuator.
assignment tools suitable for this purpose.
function of your mounting kit, if available.
display of the previous positioner. Note down the read value.
previous positioner.
moving the friction clutch.