Siemens SIPART PS2 Operating Instructions Manual page 135

Electropneumatic positioners with profibus pa
Hide thumbs Also See for SIPART PS2:
Table of Contents

Advertisement

9. Press the
10.Determine the upper endstop of the actuator. Move the actuator to the desired position
11.Press the
12.The initialization process is automatically resumed. Initialization steps "RUN1" to "RUN5"
Aborting the manual initialization process
1. Press the
2. Exit the "Configuration" mode. To do this, press the
3. The software status is displayed.
4. After releasing the
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
button. The current position of the actuator is applied. The display shows the
following:
Note
Fault message "RANGE"
The selected end position is beyond the permissible measuring range if the "RANGE"
message is output on the display. Correct the settings as follows:
1. Move the friction clutch until the display shows "OK".
2. Press the
button.
3. Move the actuator to another position using the
4. Abort the manual initialization process by pressing the
5. Then return to "P manual mode".
6. Correct the actuator travel and the position detection.
using the
or
button.
button. The current position of the actuator is applied.
are output in the bottom line of the display. The following display indicates that the
initialization has been completed successfully:
button. The display shows the "INITM" parameter. The positioner is in the
"Configuration" mode.
button, the positioner is in "P manual mode". "P manual mode" means
that the positioner has not been initialized.
7.6 Commissioning part-turn actuators
or
button.
button.
button for at least 5 seconds.
Commissioning
135