Device features
①
②
③
Figure 4-13
The slotted initiator alarm module, SIA module for short, consists of three binary outputs
Procedure for installing the slot initiator alarm module
1. You have performed the steps described in the section General information about the
2. Disconnect all electrical connections of the basic electronics.
3. Loosen the two fixing screws of the basic electronics.
4. Remove the basic electronics.
5. Insert the SIA module from the top up to the upper printed circuit board guide of the rack.
6. Slide the SIA module in the printed circuit board of the rack approximately 3 mm to the right.
7. Screw in the special screw
SIPART PS2 with PROFIBUS PA
Operating Instructions, 02/2016, A5E00127926-AB
Actuating disk bearings
Special screw
Pin
SIA module
installation of option modules (Page 54).
②
special screw
with a torque of 2 Nm.
Note
Pin in the actuating disk bearing
③
A pin
is pressed in the actuating disk bearing
③
1. Align pin
before placing the adjustment screw
2. Rotate the actuating disk bearing
③
the pin
is inserted into the special screw
④
Upper actuating disk for limit L1, terminals 41/42
⑤
Lower actuating disk for limit L2, terminals 51/52
⑥
Binary outputs
②
through the SIA module into the positioner shaft. Tighten the
①
①
and the special screw
②
Installing/mounting
4.7 Installing the optional modules
.
②
into the actuating disk bearing
②
simultaneously so that
.
⑥
.
①
.
65