4.13.4 Manual adjustment

The actuator's internal stroke position measurement is inactive during manual
adjustment.
The position feedback changes to 0% once the manual adjuster is pressed and
remains on the value during manual adjustment. The actuator detects manual
action based on the deviation between the setpoint and the stroke position and
after 10 seconds reports in register 769 with the warning "Mechanical error, device
blocked, manual intervention or calibration". The actuator LED blinks green, the
cable adapter LED is red.
Upon return to automatic mode, the actuator synchronizes to stroke position 0%.
After the synchronization, the actuator follows the pending setpoint, the actuator
LED changes to continuous green and the cable adapter LED blinks green
(communication active). The warning in register 769 is reset.

4.13.5 Parameters and function description

Reg.
Name
Process values
1
Setpoint
2
Forced control
3
Actual value
256
Command
Parameters
259
Op mode
260
MinPosition
261
MaxPosition
262
Actuator runtime
263
Positioning signal
characteristic
between Y and U
264
Tolerance blockade
monitoring
513
Backup mode
514
Backup position
515
Backup timeout
516
Startup setpoint
764
Modbus address
765
Baud rate
766
Transmission
format
767
Bus termination
768
Bus config.
command
769
Status
Actuators SAX.., SAY.., SAV.., SAL.. for valves
Functions and control
R/W
Unit
Scaling
RW
%
0.01
RW
--
--
R
%
0.01
RW
--
R
--
--
R
%
0.01
R
%
0.01
R
s
1
R
--
--
R
%
0.01
RW
--
--
RW
%
0.01
RW
s
1
RW
%
0.01
RW
--
--
RW
--
--
RW
--
--
RW
--
--
RW
--
--
--
--
R
Range / listing
0...100
0 = Off / 1 = Extend / 2 = Retract
3 = Stop
0...100
0 = Ready or calibration in progress /
1 = Not available / 2 = Self test
3 = Reinitialize / 4 = Remote reset
1 = POS
0...100
0...100
30
0 = Linear (e.g. SAX61../MO + V_G41)
1 = Logarithmic (e.g. SAS61../MO + V_G44)
4
0 = Move to backup position
1 = Maintain last position / 2 = Disable
0...100
60...900
0...100
1...248 / 255 = "unassigned"
0 = auto / 1 = 9600 / 2 = 19200 3 = 38400
4 = 57600 / 5 = 76800 / 6 = 115200
0 = 1-8-E-1 / 1 = 1-8-O-1 / 2 = 1-8-N-1 / 3 = 1-8-N-2
0 = Off / 1 = On
120 Ω electronically switchable
0 = Ready / 1 = Load / 2 = Reject
See Section, Register 769 "Status"
CE1P4040en
2018-12-05
69 / 92