Power On/Off and Check Items
4.4.2 Check on External Safety Circuit
Make a check on the safety circuit recommended by the motor manufacturer, which include a
check on the disconnection of the power supply to the motor driver with CW and CCW drive
inhibition switch input from an external circuit.
4.4.3 Check on Safety Circuit with Positioning Unit
Step 1
Forcibly operate the over limit switch for the positioning safety circuit and check that the
positioning unit correctly receives limit input.
The state of limit input can be checked with the input contact. The valid logic of limit input can
be changed in the parameter-setting menu of the Configurator PM7.
Step 2
Input a program, if necessary, to perform the JOG operation of the positioning unit. Then
forcibly operate limit input and check that the motor will come to a stop.
You can use the tool operation of the Configurator PM7 to make a check without using a
program.
Step 3
Perform the JOG operation of the positioning unit and check that the over limit switch will
operate normally.
Positioning unit
Operation at limit input
Condition
When JOG operation
is executed
During JOG operation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
4-8
To motor driver
Direction
Forward rotation
Limit input (+):ON
Limit input (-):ON
Reverse rotation
Limit input (+):ON
Limit input (-):ON
Forward rotation
Limit input (+):ON
Reverse rotation
Limit input (-):ON
Over limit switch
Connect to the positioning unit
Limit status
Not executable, Error occurs.
Executable
Executable
Not executable, Error occurs.
Deceleration stop, Error occurs.
Deceleration stop, Error occurs.
Over limit switch
Operation