2-2-2

E5CD-B Terminal Block Wiring Example

 Terminal Arrangement
The terminals block of the E5CD-B is divided into five types of terminals: control output 1, sensor input, auxiliary
outputs, input power supply, and options.
Control output 1
Not used.
Sensor input
Precautions for Correct Use
When you purchase the Digital Controller, it will be set for a K thermocouple (input type = 5). If a
different sensor is used, an input error () will occur. Check the setting of the Input Type
parameter.
Control Output 1
 Model Numbers
The control output 1 specification of the E5CD-B is given in the following location in the model number.
E5CD-@@ @ @ B M-@@@
Code
RX
1 relay output
QX
1 voltage output (for driving SSR)
CX
1 linear current output
 Terminal Details
Control output 1
E5@D Digital Temperature Controllers User's Manual (H224)
17
1
18
2
19
3
20
4
21
5
22
6
23
7
24
8
Control outputs 1
Output type
RX
A
Control output 1
Relay output
B
9
10
Auxiliary outputs
11
12
13
14
Input supply
15
16
Options
Specification
250 VAC, 3 A (resistive load)
12 VDC, 21 mA
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω
max.
QX
A
+
Voltage output
B
(for driving SSR)
2 Preparations
CX
A
+
Linear current
Control output 1
B
output
2 - 13