6 Parameters
Setting
*1
PRST (Program Start) can be set even when the Program Pattern parameter is set to OFF, but
the function will be disabled.
*2
This function can be set for heating/cooling control, but the function will be disabled.
*3
This function can be set only for a Controller that supports communications. Also, when a work
bit is selected as the event input data for a logic operation, Communications Write
Enable/Disable cannot be assigned. If the Digital Controller is operating only on the power
supply from the USB-Serial Conversion Cable, it will operate as if the event inputs remain OFF.
Therefore, communications writing will be disabled and you will not be able to write data from
Setup Tools, such as the CX-Thermo.
*4
The following table shows the relationships between the ON/OFF status of multi-SP number
switching bits 0 to 2 and the set point.
Selected set point
Note: Any bits that are not assigned to event inputs are treated as being OFF.
 Related Parameter
See
See
SP 0 to 7 (Adjustment Level): Page 6-22
6 - 58
Setting
None
none
RUN/STOP
stop
Auto/Manual
manu
prst
Program Start
Invert Direct/Reverse Operation
drs
None
nont
100% AT Execute/Cancel
at-2
at-1
40% AT Execute/Cancel
Setting Change Enable/Disable
wtpt
cmwt
Communications Writing Enable/Disable
Alarm Latch Cancel
lat
msp0
Multi-SP No. Switching Bit 0
msp1
Multi-SP No. Switching Bit 1
msp2
Multi-SP No. Switching Bit 2
RUN/STOP
run
PID Update (Adaptive Control)
a-ud
Automatic Filter Adjustment
fa
Water-cooling Output Adjustment
w-ht
Bit 0
SP 0
OFF
SP 1
ON
SP 2
OFF
SP 3
ON
SP 4
OFF
SP 5
ON
SP 6
OFF
SP 7
ON
Function
*1
*2
*3
*4
*4
*4
Multi-SP No. switching bits
Bit 1
OFF
OFF
ON
ON
OFF
OFF
ON
ON
E5@D Digital Temperature Controllers User's Manual (H224)
Bit 2
OFF
OFF
OFF
OFF
ON
ON
ON
ON