5 Advanced Operations
• Checking and Resetting the Control Output 1 ON/OFF Count Monitor
1
Press the M Key several times in the Advanced Function Set-
ting Level to display ra1m (Control Output 1 ON/OFF Count
Monitor).
2
Check the control output 1 ON/OFF count.
Every 100 operations is one count.
Therefore, in the example on the right, the ON/OFF count is
between 100 and 199 times.
3
Press the M Key several times to select rac (ON/OFF Counter
Reset).
Press the U or D Key to select "1." The Control Output 1 ON/OFF
Count Monitor parameter will be reset to 0. Press the U or D Key
to select "2." The Control Output 2 ON/OFF Count Monitor
parameter will be reset to 0. The display will return to 0 after the
counter is reset.
5 - 24
Advanced Function Setting
Level
ra1m
0000
ra1m
0001
Advanced Function Setting
Level
rac
0001
E5@D Digital Temperature Controllers User's Manual (H224)
Control Output 1
ON/OFF Count
ON/OFF
Counter Reset