Omron E5*D series User Manual page 244

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

6 Parameters
 Related Parameters
See
See
Process Value/Set Point (Operation Level): Page 6-8
SP Ramp Set Value (Adjustment Level): Page 6-34
SP Ramp Fall Value (Adjustment Level): Page 6-34
Set Point Upper Limit (Initial Setting Level): Page 6-43
Set Point Lower Limit (Initial Setting Level): Page 6-43
ct1
This parameter measures the heater current from the CT input used for detecting heater burnout.
This parameter measures and displays the heater current value.
• Heater burnout is not detected if the ON time for the control output for heating is 100 ms
or less (30 ms or less if the control period is 0.1 or 0.2 s).
Function
Monitor
• ffff is displayed when 55.0 A is exceeded.
• If an alarm is output for the Heater Burnout Detection 1 parameter, the No. 1 display will
flash the Heater Current 1 Value Monitor parameter.
 Related Parameters
See
See
Heater Burnout Detection 1 (Adjustment Level): Page 6-20
HB ON/OFF (Advanced Function Setting Level): Page 6-66
Error Display ct1: Page A-18
lcr1
This parameter measures the heater current from the CT input used for detecting SSR short-circuits.
The heater current is measured and the leakage current 1 monitor is displayed.
• The HS alarm is not detected if the OFF time for the control output for heating is 100 ms
or less (38 ms or less if the control period is 0.1 or 0.2 s).
Function
Monitor
• ffff is displayed when 55.0 A is exceeded.
• If an alarm is output for the HS Alarm 1 parameter, the No. 1 display will flash the
Leakage Current 1 Monitor parameter.
 Related Parameters
See
See
HS Alarm 1 (Adjustment Level): Page 6-21
HS Alarm Use (Advanced Function Setting Level): Page 6-76
Error Display lcr1: Page A-18
6 - 10
Heater Current 1 Value Monitor
Monitor range
0.0 to 55.0
Leakage Current 1 Monitor
Monitor range
0.0 to 55.0
HB and HS alarms must be supported.
The HB ON/OFF parameter must be set to ON.
Unit
A
HB and HS alarms must be supported.
The HS Alarm Use parameter must be set to ON.
Unit
A