Omron E5*D series User Manual page 290

Digital temperature controllers
Hide thumbs Also See for E5*D series:
Table of Contents

Advertisement

6 Parameters
tr-h
tr-l
• This parameter sets the upper and lower limit values of transfer outputs.
Function
Setting
output type
Set point
Set point
during SP
ramp
PV
MV
(heating)
MV
(cooling)
Valve
opening
*1
This function can be set for standard control Model, but the setting will be disabled.
 Related Parameter
See
See
Transfer Output Type (Initial Setting Level): Page 6-55
6 - 56
Transfer Output Upper Limit
Transfer Output Lower Limit
Transfer
Setting range
SP lower limit to SP upper limit
SP lower limit to SP upper limit
Temperature
Input setting range
input
lower limit to input
setting range upper
limit
Analog input
Analog scaling
lower limit to analog
scaling upper limit
Standard
−5.0 to 105.0
Heating/
0.0 to 105.0
cooling
Position-
−10.0 to 110.0
proportional
*1
control
000
There must be a transfer output.
The transfer output type must not be set to OFF.
000
Transfer
output lower
limit
SP lower limit
Input setting
range lower limit
Scaling lower
limit
0.0
E5@D Digital Temperature Controllers User's Manual (H224)
Default
Transfer
Unit
output upper
limit
SP upper limit
EU
Input setting
range upper
limit
Scaling upper
limit
100.0
%