2 Preparations
Sensor Input
 Model Numbers
All E5CD models have universal sensor inputs, so the code in the model number is always "M."
E5CD-@@ @ @ @ M-@@@
 Terminal Details
Do not connect anything to the terminals that are shaded gray.
TC (thermocouple)
+
Precautions for Correct Use
• When complying with EMC standards, the line connecting the sensor must be 30 m or less. If
the cable length exceeds 30 m, compliance with EMC standards will not be possible.
• The sensor input is not electrically isolated from the internal circuits. If you use a grounded
thermocouple, do not connect one of the sensor input terminals to ground. (If the sensor input
terminals are connected to ground, errors will occur in the measured temperature as a result
of leakage current.)
2 - 10
Sensor input
Pt (resistance
thermometer)
D
D
A
E
B
E
F
B
F
I (current)
+
D
mA
E
F
E5@D Digital Temperature Controllers User's Manual (H224)
V (voltage)
D
E
V
F
+