• The manual control level display appears as shown below.
Function
Process value
Set point
MV (Manual MV)
*
 Related Parameters
See
See
5-16 Performing Manual Control: Page 5-56
Standard or Heating/Cooling (Initial Setting Level): Page 6-44
E5@D Digital Temperature Controllers User's Manual (H224)
PV/MV (Manual MV)
E5ED or E5ED-B
25
100
50.0
PV/SP/Manual MV
Temperature: According to indication range for each sensor.
Analog: Scaling lower limit −5% FS to Scaling upper limit +5% FS
(Refer to A-8 Sensor Input Setting Range, Indication Range, Con-
trol Range.)
SP lower limit to SP upper limit
Standard control
Heating/cooling control
When the Manual MV Limit Enable parameter is set to ON, the setting range will be the MV
lower limit to the MV upper limit.
The control must be set to 2-PID control.
E5CD or E5CD-B
25
50.0
PV/Manual MV
Monitor range
Setting range
*
−5.0 to 105.0
−105.0 to 105.0
6 Parameters
Unit
EU
EU
Default
Unit
0.0
%
*
6 - 39
6